Analogue converter flowmeter

flowmeters-homeright.jpg

Flowmeters: Analogue converter flowmeter:

  • 0/4-20mA, 0-5V or 0-10V
  • IP65 (Nema 4X)
  • Non volatile memory
  • 15-24V dc operation
  • Pulse input
  • Output damping
  • 0 - 50°C
  • Competitively priced
  • Wall mounting
  • 4 frequency ranges
  • Sensor PSU (5V)
  • Separate zero & span adjustments
  • Pulse input indicator
  • Output status LED
  • Ideal for:
    • Data monitoring
    • Test rigs
    • Control systems

Flowmeters: Analogue converter: Specification

Power
15 - 24 V dc

Output
0/4 to 20mA
0 to 5 Vdc
0 to 10 V dc

Signal
Pulse input compatible with reed switch, Hall effect or optical detectors

Display
Status LEDs
Red for output errors
Green for signal input.

Enclosure
IP66 (NEMA 4X) High impact glass polymer.

Temp
0°C to +50°C.

Frequency range
0.25/0.5 - 1KHz. Selectable. In four ranges. Output damping for low frequencies

Sensor Supply
5 volts regulated up to 50mA

Flowmeters: Analogue converter - Order codes

  • 370-005 0/4-20mA
  • 370-006 0-10V
  • 370-007 0-5V

Flowmeters: Analogue converter: Standard Materials of construction

UV resistant polycarbonate case, stainless steel screws.

Flowmeters: Analogue converter:



This simple wall, or in some cases, flowmeter mounted instrument gives an analogue output proportional to flow. Three basic models are available offering 0/4 to 20 milliamp, 0 to 5 volt and 0 to 10 volt outputs. In all cases the offset and full scale adjust-ments are independent of each other. The standard converter has an input frequency range of 0.5 to 1 KHz. This is select-able via a pair of DIL switches. A special lower range version is available for use with lower frequency inputs such as positive displacement flowmeters, this device operates down to 0.25 Hz. At these very low frequencies the output can be “damped”. Two status LEDs indicate whether pulses are being received and if the output is operating within its selected flow range. The en-closure is a high impact polymer that seals the unit to IP65 (NEMA 4X). Access to the terminals is via a pair of glands on the bottom of the enclosure.

Titan flowmeters - analogue converter

Titan flowmeters - analogue converter

Titan flowmeters Analogue Converter calibration

As with nearly all of our products calibration is performed for you at our factory on equipment that has traceable calibrations to national standards. If for any reason the analogue converter re-quires re-calibration in situ the following procedure may be fol-lowed.

1. Select from the chart below the anticipated operating range for the converter.

2. With no pulse input (or your minimum) set the zero flow output. This may be 0 volts, 0mA or 4mA depending on the requirements.

3. Set the flow to your maximum or inject a frequency equivalent to this and adjust the span potentiometer to give your required full scale.

4. If the output LED shows an over or under range status select the next frequency range up or down and start again.

Frq. Range Sw1 Sw2 Sw3 Sw4
5-25 Hz
20-80 Hz
70-245 Hz
225-850 Hz
off
on
off
off
off
off
on
on
off
off
off
off
off
off
off
off
For low frequency use, Sw4 on reduces output jitter